Catalog navigation
CAD model selection
Selectable products: 18
HELP_VARIABLE
item number
300325
u
Device type
115/86 classic
u
Level of detail
position
Width
950
u
mm
Hieght
680
u
mm
depth
350
u
mm
Curb weight
56
u
kg
nominal voltage
230 V AC
Max. permissible buffer temperature
95 °C
Max. permissible operating temperature primary
90 °C
Max. permissible operating temperature secondary
80 °C
Max. permissible operating pressure primary
6 bar
Max. permissible operating pressure secondary
10 bar
KVS value primary
12,3
u
KVS value secondary
6,6
u
∆pV primary
23,8
u
kPa
∆pV secondary
52,8
u
kPa
Connection side
right/left
Nominal size ball valve heating flow / heating return
DN 40 (1 1/2" IG)
u
Nominal size ball valve cold water / hot water
DN 40 (1 1/2" IG)
u
Nominal size ball valves circulation
DN 25 (1" IG)
Drinking water UBA conformity
yes
Manufacturing tolerances
+/- 10 mm
Cover
yes
Plate heat exchanger
Copper / stainless steel
Primary pump
Wilo Stratos Para 30/1-8 T11 (PWM2)
u
Circulation pump
Wilo Yonos Para Z25/7.0
Flow sensor
5-80
u
l/min
Flow 10/45 ° C at primarily 55 ° C
/ l/min
NL number
/
power
/ kW
Flow primarily 55 ° C
/ l/h
Flow 10/45 ° C at primarily 70 ° C
/ l/min
NL number
/
power
/ kW
Flow primarily 70 ° C
/ l/h
Keywords / synonyms
Fresh water module, fresh water modules, fresh water station, fresh water stations, fresh water system, fresh water systems
Product information
PDF data sheet
Tender text
115/86 classic
u
Manufacturer website
Info Link
Installation / operating instructions
installation Guide
Support
Preview - Generation
Quotation
3D
Dimension

Additional Information